TECHNICAL & SERVICE MANUAL
OUTDOOR UNIT : AE2MI40AH
AE2MI56AHB
AE3MI68AH
AE4MI80AH
AE2MI40AH
AE4MI80AH
AE2MI56AHB
AE3MI68AH
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
Outdoor Model No.
AE2MI40AH
AE2MI56AHB
AE3MI68AH
AE4MI80AH
Capacity
4.0kW
5.6kW
6.8kW
8.0kW
Product Code No.
3 870 310 85 (1 852 349 45)
3 870 310 86 (1 852 349 46)
3 870 310 87 (1 852 349 47)
3 870 310 88 (1 852 349 48)
REFERENCE NO. SM700738
< Applicable Indoor Units >
Wall mounted type
For details about the combination, refer to
"Unit Combination Table" in the Appendix of
this manual.
AWMI22AHL
AWMI27AHL
AWMI35AHL
AWI52AHL
AWI68AHL
NOTE
Destination: Europe
RoHS
WARNING
This product does not contain any hazardous substances prohibited by the RoHS Directive.
• You are requested to use RoHS compliant parts for maintenance or repair.
• You are requested to use lead-free solder.
FILE NO.
Do not vent R410A into atmosphere : R410A is a fluorinated greenhouse gas,
covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 1975.
F-GAS REGULATION (EC) No 842 / 2006
Zobrazit stránku 0
1 2 3 4 5 6 ... 101 102

Shrnutí obsahu

Strany 1 - AE4MI80AH

TECHNICAL & SERVICE MANUALOUTDOOR UNIT : AE2MI40AHAE2MI56AHBAE3MI68AHAE4MI80AHAE2MI40AHAE4MI80AHAE2MI56AHBAE3MI68AHDC INVERTER MULTI-SYSTEM AIR CO

Strany 2 - Please Read Before Starting

Outdoor Unit AE4MI80AHIndoor Unit AWMI27AHL × 4DATA SUBJECT TO CHANGE WITHOUT NOTICE.CompressorRefrigerant / Amount charged at shipment kgRefrigerant

Strany 3 - Table of Contents

Pub. OI-85264181052000Via Varese, 90 - 21013 Gallarate (VA) - ItalyTel. +39 0331 755111 - Fax +39 0331 776240http://www.argoclima.comAE4MI80AH• Refer

Strany 4

Table 1Room Room Room Room Room Room Room RoomABCDCapacity ( Min. - Max. ) A B C D Capacity ( Min. - Max. )2.2 = 2.2 2.2 2.2 ( 1.5 - 2.6 ) 2.5 2.5 ( 1

Strany 5 - APPLICABLE INDOOR UNITS

Via Varese, 90 - 21013 Gallarate (VA) - ItalyTel. +39 0331 755111 - Fax +39 0331 776240http://www.argoclima.com

Strany 6 - 1. OPERATING RANGE

Outdoor Unit AE2MI40AH2-2-1. Outdoor UnitControl PCBControl Circuit Fuse ControlsPart No.Microprocessor250V 25ACB-CMRV1424EHDATA SUBJECT TO CHANGE WI

Strany 7 - 2. SPECIFICATIONS

Outdoor Unit AE2MI56AHBControl PCBControl Circuit Fuse ControlsPart No.Microprocessor250V 25ACB-CMRV1924EHcc FV50S ... 900 Compressor Oil ... Amoun

Strany 8 - × 1 + AWI52AHL × 1

Outdoor Unit AE3MI68AHControl PCBControl Circuit Fuse ControlsPart No.Microprocessor250V 25ACB-CMRV2444EHcc FV50S ... 900 Compressor Oil ... Amount

Strany 9 - × 3 + 12.7 (1/2") × 1

Outdoor Unit AE4MI80AHControl PCBControl Circuit Fuse ControlsPart No.Microprocessor250V 25ACB-CMRV3144EHcc FV50S ... 1,200 Compressor Oil ... Amou

Strany 10 - × 2 + 12.7 (1/2") × 2

2-3. Other Component Specifications0010203040506070809040608010012014016018020020Resistance (k ohm)Temperature (°C)4035302520151050-20-15-10-50 51015

Strany 11 - 2-2-1. Outdoor Unit

295608 85790 70463363102854-ID:23.6ID:182-ID:125691570122158 7014246Wide tube service valvedia.9.52 (3/8") × 2Narrow tube service valvedia.6.35

Strany 12 - Outdoor Unit AE2MI56AHB

293608 13612900 8535369345320ID:185-ID:23.67401875113150 7211451Wide tube service valvedia.9.52 (3/8") × 2Narrow tube service valvedia.6.35 (1/4

Strany 13 - Outdoor Unit AE3MI68AH

293608 1361235369345320ID:185-ID:23.6900 857401875 70113150 7270114517070Wide tube service valvedia.9.52 (3/8") × 3Narrow tube service valvedia.6

Strany 14 - Outdoor Unit AE4MI80AH

293608 1361235369345320ID:185-ID:23.6900 858901875 70113150 7370114517070Wide tube service valvedia.9.52 (3/8") × 2Narrow tube service valvedia.6

Strany 15

When WiringELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.SP

Strany 16 - Outdoor Unit AE2MI40AH

4. REFRIGERANT FLOW DIAGRAM4-1. Refrigerant Flow DiagramOutdoor Unit AE2MI40AHInsulation of Refrigerant TubingBecause capillary tubing is used in th

Strany 17 - Outdoor Unit AE2MI56AHB

Narrow tubeO.D.6.35mmO.D.6.35mmOutdoor Unit AE2MI56AHBInsulation of Refrigerant TubingBecause capillary tubing is used in the outdoor unit, both thewi

Strany 18 - Outdoor Unit AE3MI68AH

Outdoor Unit AE3MI68AHInsulation of Refrigerant TubingBecause capillary tubing is used in the outdoor unit, both thewide and narrow tubes of this air

Strany 19 - Outdoor Unit AE4MI80AH

Outdoor Unit AE4MI80AHInsulation of Refrigerant TubingBecause capillary tubing is used in the outdoor unit, both thewide and narrow tubes of this air

Strany 20 - Indoor unit Outdoor unit

5. PERFORMANCE DATA5-1. Temperature Charts5-1-1. Temperature Charts (AE2MI40AH)Outdoor Unit AE2MI40AH Indoor Unit AWMI22AHL × 1Cooling Char

Strany 21

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)(1

Strany 22

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)(1

Strany 23

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)•

Strany 24 - 5-1. Temperature Charts

• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.• Che

Strany 25 - Heating Characteristics

Outdoor Unit AE2MI56AHB Indoor Unit AWMI35AHL × 1Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)Heating Characterist

Strany 26

Table of Contents APPLICABLE INDOOR UNITS1. OPERATING RANGE2. SPECIFICATIONS2-1. Unit Specifications 2-2. Major Component Specifications 2-3.

Strany 27

Outdoor Unit AE2MI56AHB Indoor Unit AWI52AHL × 1Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)Heating Characteristi

Strany 28

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)(1

Strany 29

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)(1

Strany 30

Outdoor Unit AE3MI68AH Indoor Unit AWMI35AHL × 1Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)Heating Characteristi

Strany 31

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)(1

Strany 32

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)(1

Strany 33

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)(1

Strany 34

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)(1

Strany 35

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)(1

Strany 36

30 35 4025Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230

Strany 37

APPENDIX A INSTALLATION INSTRUCTIONS APPENDIX B UNIT COMBINATION TABLESA-1A-2...

Strany 38

30 35 4025Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230

Strany 39

WARNINGTo avoid electrical shock hazard, be sure todisconnect power before checking, servicingand/or cleaning any electrical parts.6. ELECTRICAL DATA

Strany 40

WARNINGTo avoid electrical shock hazard, be sure todisconnect power before checking, servicingand/or cleaning any electrical parts. Outdoor Unit AE2MI

Strany 41 - 6. ELECTRICAL DATA

WARNINGTo avoid electrical shock hazard, be sure todisconnect power before checking, servicingand/or cleaning any electrical parts. Outdoor Unit AE3MI

Strany 42

WARNINGTo avoid electrical shock hazard, be sure todisconnect power before checking, servicingand/or cleaning any electrical parts. Outdoor Unit AE4MI

Strany 43

7. FUNCTIONS7-1. Explanation of FunctionsThe numerical values such as temperature, frequency, time and current in parentheses are an example of AE4M

Strany 44

Control/conditionsHEATWhen defrost operation begins, frost has formed on the outdoor unit (when the ambient air temperature is low).Defrost operation

Strany 45 - 7. FUNCTIONS

Control/conditionsCOOLThe ON/OFF operation button on the remote controller is pressed.The room temperature has reached the desired temperature.The out

Strany 46

Control/conditionsSENSOR DRY(1/f fluctuation fan)The ON/OFF operation button on the remote controller is pressed.The outdoor unit does not operate for

Strany 47

7-2. Protective Functions7-2-1. Defrost Detection and Release(2) Clean defrostIf all indoor units are stopped during HEAT operation, and frost is de

Strany 48 - 1/f fluctuation fan

APPLICABLE INDOOR UNITSAE2MI40AHMulti-Outdoor UnitIndoor UnitYES YES YES NO NOAE2MI56AHB YES YES YES YES NOAE3MI68AH YES YES YES YES YESAE4MI80AH2

Strany 49 - 7-2. Protective Functions

7-2-2. Current ControlThe operating current may rise as a result of causes including increasing heating or cooling loads or decreases in power voltag

Strany 50 - 7-2-2. Current Control

7-2-5. Control at HEAT Start-upIf HEAT operation is started when the outdoor air temperature is 15 °C or below, the unit operates at the HEAT start-u

Strany 51 - 7-2-3. Low Start Current

8. TROUBLESHOOTING8-1. Precautions before Performing Inspection or RepairBoth the indoor unit and outdoor unit include electronic control circuits.

Strany 52 - 8. TROUBLESHOOTING

8-2. Trouble Diagnosis by Error Monitor LampsWARNINGTo prevent electric shock, do not inspect or repair until the Power Lamp on the P.C.Board is turn

Strany 53

8-3-1. Checking the outdoor unit8-3. Checking the Outdoor System8-3-2. Checking the defrost operationWork procedureApply 220 V AC between terminals

Strany 54

8-4. Trouble Diagnosis of Each Part8-4-1. Problems of Each Part and Inspection PointsFor details about the inspection points, refer to the Inspectio

Strany 55

8-4-2. Inspection Points for Each Part(1) Outdoor control circuit boardRefer to 8-3-1. Checking the outdoor unit.(2) FuseCheck it visually or the con

Strany 56

(8) Branch tubing temperature sensorCheck that the sensor is securely contained in the thermostat holder.(9) BreakerCheck whether or not the breaker h

Strany 57

8-5. Trouble Diagnosis of Fan MotorThis outdoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil resi

Strany 58

ADFlare tool for R410AADConventional flare tool (R22)Spacer9. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT9-1. Characteristics of New

Strany 59 - 9. REFRIGERANT R410A:

1. OPERATING RANGEMaximumMinimumMaximumMinimum32 °C D.B. / 23 °C W.B.19 °C D.B. / 14 °C W.B.27 °C D.B.16 °C D.B.43 °C D.B.19 °C D.B.24 °C D.B. / 18 °

Strany 60

Tubing precautionsRefrigerant R410A is more easily affected by dust or moisture compared with R22, thus be sure to temporarily cover the ends of the t

Strany 61

9-3. Tools Specifically for R410A For servicing, use the following tools for R410AGauge manifoldCharging hoseGas leak detectorRefrigerant cylinderCha

Strany 62

9-5. In Case of Compressor Malfunction CAUTIONShould the compressor malfunction, be sure to make the switch to a replacement compressor as quickly as

Strany 63

ValveSingle valveCharge liquid refrigerant with cylinder in up-side-down position.Single valve (with siphon tube)Charge with cylinder in normal positi

Strany 64

Length of tubingEvacuation timeLess than 10 metersMore than 10 minutesMore than 10 metersMore than 15 minutes9-6. In Case Refrigerant is LeakingCAUTI

Strany 65 - 9-8-1. Use of Existing Units

9-7. Charging Additional Refrigerant9-7-1. When Tubes are ExtendedObserve the proper amount of refrigerant as stated in this service manual or the i

Strany 66 - (II-852-6-4190-444-00-0)

INSTALLATION INSTRUCTIONSAE2MI40AHAE2MI56AHBAE3MI68AHAE4MI80AH(II-852-6-4190-444-00-0)APPENDIX AA-1

Strany 67 - INSTALLATION INSTRUCTIONS

ContentsPageIMPORTANT!Please Read Before Starting ... 21. GENERAL ...

Strany 68 - IMPORTANT!

2EnglishIMPORTANT! Please Read Before StartingThis air conditioning system meets strict safety and oper-ating standards. As the installer or service p

Strany 69 - 1. General

3English1. GeneralThis booklet briefly outlines where and how to installthe air conditioning system. Please read over theentire set of instructions f

Strany 70

2. SPECIFICATIONS2-1. Unit SpecificationsOutdoor Unit AE2MI40AHIndoor Unit AWMI27AHL × 2DATA SUBJECT TO CHANGE WITHOUT NOTICE.CompressorRefrigerant

Strany 71

4English1-5. Additional Materials Required for Installation1. Refrigeration (armored) tape2. Insulated staples or clamps for connecting wire(See loca

Strany 72

5EnglishG Install the indoor unit more than 1 meter away from anyantenna or power lines or connecting wires used for tele-vision, radio, telephone, se

Strany 73

6English(A)Fig. 4dø9.52Unionø12.70Flare(ø12.70 ø9.52) Supplied Reducerø9.52ø9.52ø6.35ø9.52ø6.35ø9.52ø6.35Cø9.52Bø12.70A(AWMI22/27/35AHL)(AWMI22/2

Strany 74

(A)Fig. 4hø9.52Unionø12.70Flare(ø12.70 ø9.52) Supplied Reducerø9.52ø9.52ø6.35ø9.52ø6.35ø9.52ø6.35Cø12.70Bø12.70A(AWMI22/27/35AHL)(AWMI22/27/35AHL

Strany 75 - About 40 cm

8English(C)Fig. 4jø9.52ø9.52ø6.35ø12.70ø6.35ø12.70ø6.35Cø12.70Bø12.70A(AWI52AHL)(AWMI22/27/35AHL)ø9.52ø9.52ø6.35DOutdoor unit Indoor unit(AWMI22/27/35

Strany 76

Air intake Min. 10 cmAir dischargeMin.5 cmMin.40 cmValvesideMin. 25 cmMin.2 mMin.2 mGroundObstacleObstacle aboveAir dischargeMin. 10 cmAir intake9Engl

Strany 77 - Over 40cm

10English(2) AE2MI56AHB(3) AE3MI68AH(4) AE4MI80AH2-4. Outer Dimensions of Outdoor Unit6081361232034536990074085A11451150 72 707011375 7070Service val

Strany 78 - Over 50cm

11English2-5. Diagram of Outdoor Unit InstallationNever install only a single indoor unit.Be sure to connect indoor and outdoor units only in combina

Strany 79 - 3. Installation Process

12EnglishBe sure to connect indoor and outdoor units only in combinations that are listed in the catalog or in the combination table that was provided

Strany 80 - Service valve on

13English3. Installation Process3-1. Embedding the Tubing and WiringG Do not connect tubes to locations that are embedded.G Be sure to bind refriger

Strany 81 - Apply putty here

Outdoor Unit AE2MI56AHBIndoor Unit AWMI27AHL × 1 + AWI52AHL × 1DATA SUBJECT TO CHANGE WITHOUT NOTICE.CompressorRefrigerant / Amount charged at shipmen

Strany 82

14EnglishWhen reaming, hold the tube end downward and be surethat no copper scraps fall into the tube. (Fig. 9)(3) Remove the flare nut from the unit

Strany 83 - 20 min. or more

15English3-7. Insulation of Refrigerant TubingTo prevent heat loss and wet floors due to dripping of con-densation, both tubes must be well insulated

Strany 84 - Pump Down

16English4. Air PurgingAir and moisture remaining in the refrigerant sys-tem have undesirable effects as indicated below. Therefore, they must be pur

Strany 85 - 5. Wiring Instructions

17English(4) With the “Lo” knob of the manifold valve open andhigh-pressure valve (“Hi”) closed completely, runthe vacuum pump. Run the pump until the

Strany 86

18EnglishI Pump DownG When relocating or disposing of the Air Conditioner, requestthis service from the dealer where the unit was purchased,or from an

Strany 87

19English5. Wiring Instructions5-1. General Precautions on Wiring(1) Before wiring, confirm the rated voltage of the unit asshown on its nameplate,

Strany 88 - 1 2 3

20EnglishWARNINGG Be sure to comply with local codes on runningthe wire from the indoor unit to the outdoor unit(size of wire and wiring method, etc.)

Strany 89 - 6. Test Run

21EnglishWhen connecting each power wire to the correspondingterminal, follow the instructions “How to connect wiringto the terminal” and fasten the w

Strany 90 - 8. Installation Check Sheet

22English123123123123Indoor unit DIndoor unit BIndoor unit AIndoor unit CGroundPower: Single-phase, 220/240VAC 50HZPower switch(not provided)Outdoor u

Strany 91 - 8FA-2-5257-68200-0

23EnglishRegulations on wire size differ from locality to locality. For field wiring requirements, please refer to your localelectrical codes. Make su

Strany 92 - Meaning of Abbreviations

Outdoor Unit AE3MI68AHIndoor Unit AWMI27AHL × 3DATA SUBJECT TO CHANGE WITHOUT NOTICE.CompressorRefrigerant / Amount charged at shipment kgRefrigerant

Strany 93 - List of Combination Table

24English7. Connecting a Home Automation deviceThe HA (white) 4P terminal is located on the indoor unit PCB. If a HA device will be used, connect it

Strany 94 - AE2MI40AH

21212121BLKBLKWHTWHTWHTWHT121 2 3 4wwBLKBLKCOMPRESSORTHERMISTOR(OLR)OVERLOAD RELAYCOMPRESSORMOTORWHTRED(2P) CONNECTOR(2P) CONNECTORCOMPOLR0OLR1COIL/OU

Strany 95

26EnglishWHTWHTL2 L1WHTWHTWHT2P-CONNECTOR2121REACTANCECOILTHERMISTORCOMPCOIL/OUTDOOR A-TH B-THCOMPRESSORTHERMISTOROUTDOORTHERMISTORAW THERMISTORWWDEF1

Strany 96

UNIT COMBINATION TABLESAPPENDIX BBe sure to operate the air conditioning system only when 2 or more indoor units have been installed. If operated with

Strany 97

Pub. OI-85264181049000Via Varese, 90 - 21013 Gallarate (VA) - ItalyTel. +39 0331 755111 - Fax +39 0331 776240http://www.argoclima.comAE2MI40AH• Refer

Strany 98

Table 1Room Room Room RoomABCapacity ( Min. - Max. )ABCapacity ( Min. - Max. )2.2 = 2.2 2.2 2.2(1.2 - 2.6)2.5 2.5(1.4 - 3.5)2.65 = 2.65 2.65 2.65(1.2

Strany 99

Pub. OI-85264181050000Via Varese, 90 - 21013 Gallarate (VA) - ItalyTel. +39 0331 755111 - Fax +39 0331 776240http://www.argoclima.comAE2MI56AHB• Refe

Strany 100

Table 1Room Room Room RoomABCapacity ( Min. - Max. )ABCapacity ( Min. - Max. )2.2 = 2.2 2.2 2.2(1.4 - 2.6)2.5 2.5(1.8 -4.3)2.65 = 2.65 2.65 2.65(1.4 -

Strany 101

Pub. OI-85264181051000Via Varese, 90 - 21013 Gallarate (VA) - ItalyTel. +39 0331 755111 - Fax +39 0331 776240http://www.argoclima.comAE3MI68AH• Refer

Strany 102

Table 1Room Room Room Room Room Room Room RoomABCDCapacity ( Min. - Max.)A BCDCapacity ( Min. - Max. )2.2 = 2.2 2.2 2.2 ( 1.4 - 2.6 ) 2.5 2.5 ( 1.8 -4